9 lines of electricity, kitchen bathroom and living room cabinet machine air conditioner are 4 squar

Updated on Kitchen 2024-09-19
1 answers
  1. Anonymous users2024-01-24

    The living room, kitchen, bathroom socket should be installed with a leakage protector with an empty open 6 position, because the socket is 10A, the line is 4 square, then choose 25A. If the cabinet air conditioner socket is 16A, then the monolithic 20A air opening is selected, and the rest are all selected monolithic 16A air opening.

    The main empty selection 63A's two-way empty opening, a total of 14 bits plus 1 spare, then a total of 15 bits.