What happened to the leakage protector tripping when the air conditioner in the living room was turn

Updated on Living room 2024-06-28
7 answers
  1. Anonymous users2024-01-24

    Tripping cases include leakage, short circuit, overload, and empty opening itself.

    Problem troubleshooting: 1. The air conditioning socket will trip as soon as the electrical equipment is plugged in, and if the equipment is tripped as long as it is plugged in, no matter what the equipment is. That can almost certainly be the problem of the empty opening itself.

    2. If you just plug in the air conditioner will trip, plug in other equipment and do not jump, which can be sure that the air conditioner is leaking, check whether there are any thin copper wires in the wiring that are in contact with the outer shell of the air conditioner or very close, L and N are checked, and there will be no problems inside the new air conditioner.

    3. If you are not sure whether the plugged equipment exceeds the load of the empty opening, use the rated current of the empty opening * 220 to obtain the result. If the power of the device is greater than this number, it will definitely jump and change to a large-capacity empty opening. On the other hand, the number you get with your air conditioning power 220 is the minimum current you want to choose for air opening, and it is best to use this number * and then air open first, because the air conditioning compressor is an inductive load, and the starting current is relatively large.

    4. If you use a bulb to connect, you will jump, then it must be that the empty opening is broken or the zero line is connected wrong, and the live wire and the zero line must be opened from the same empty space.

  2. Anonymous users2024-01-23

    The biggest possibility is that the filter in the living room air conditioner is dirty, and the refrigerant cannot be circulated, causing the compressor stall current to increase, and the main switch will trip. You must ask a professional air-conditioning master to change the filter and fill it with refrigerant, and clean the heat exchanger of the external unit by the way. The refrigeration effect will be better.

  3. Anonymous users2024-01-22

    The total power of all your electrical appliances is too large It is recommended to turn off a few high-power electrical appliances to try, and if it is feasible, go to the electrical industry to change a large 10A protector.

  4. Anonymous users2024-01-21

    How big is your leakage switch! If the power is low, it will also trip! Or your thread diameter is small (the thread will be hot). Then there is the leakage, check whether the air conditioner is there and the wiring is not good.

  5. Anonymous users2024-01-20

    If the empty opening is broken, it is OK to replace it or replace it with a large one.

  6. Anonymous users2024-01-19

    It is possible that the electrical appliances in your home are used too much, resulting in excessive total power, so that the total current in the home circuit exceeds the rated current of the leakage protector, resulting in tripping. It may also be because: air conditioning heating at least once an hour to defrost, your fault suspicion is related to defrosting, defrosting four-way valve switching, resulting in an instantaneous compressor current is very large, if your air switch is small, it is possible to trip, in addition, you see whether the power line of the air conditioner is virtual, whether the empty line is virtual, and the line will jump after a long time.

  7. Anonymous users2024-01-18

    The power of the air conditioner is not too much.

Related questions
3 answers2024-06-28

The line, or the load on the socket side, is grounded or short-circuited, so it trips.

2 answers2024-06-28

The living room headlights will automatically turn off after ten minutes. >>>More

4 answers2024-06-28

and a large amount of water, the osmotic pressure in the body decreases, in order to maintain homeostatic balance, the pituitary gland secretes less antidiuretic hormone, the renal tubular collecting duct reabsorption capacity decreases, the amount of urine entering the bladder increases, and then it is time to go to the toilet.

1 answers2024-06-28

Try to sit on the toilet and don't push too hard. Of course, it also depends on your physical health and the baby's implantation. Pay attention to dietary regulation, green vegetables and fruits, avoid spicy and greasy irritating food, it is best not to eat out and eat more light diet at home, drink more water and soup, and eat some coarse grains appropriately. >>>More

4 answers2024-06-28

It has something to do with drinking less water, hot weather, and diet, plus whether the office office is sedentary for a long time? >>>More