400400 pipe 40 meters long need how much air pressure kitchen smoke exhaust

Updated on Kitchen 2024-05-21
3 answers
  1. Anonymous users2024-01-24

    The wind pressure of the fan is used to overcome the resistance of the system.

    So what you need to know is the specific friction and length.

    In order to accurately calculate the resistance, the specific friction value needs to be obtained.

    If estimated, the wind speed of the general kitchen exhaust smoke pipe is 10m s, and the specific friction resistance is 2 4Pa m.

    Specific friction resistance x length x additional coefficient) = 240Pa (external static pressure) of the selected fan: full pressure of the wind outside the machine + resistance loss of the fan itself, so the full pressure of the fan is about 350Pa, which is enough.

  2. Anonymous users2024-01-23

    400X400x4o = 6400000 cubic meters.

  3. Anonymous users2024-01-22

    Summary. The wind pressure of the fan is used to overcome the resistance of the system.

    So what you need to know is the specific friction and length.

    In order to accurately calculate the resistance, the specific friction value needs to be obtained.

    If estimated, the wind speed of the general kitchen exhaust smoke pipe is 10m s, and the specific friction resistance is 2 4Pa m.

    Specific friction resistance x length x additional coefficient) = 240Pa (external static pressure) of the selected fan wind full pressure external static pressure + fan resistance loss.

    Therefore, the full pressure of the fan is about 350Pa, which is enough.

    400400 pipe 40 meters long need how much air pressure kitchen smoke exhaust

    Hello, I have seen your question, and I will answer it for you immediately, please wait for a while The number of wind pressures of the wind turbine is only used to overcome the resistance of the system. So what you need to know is the specific friction and length. In order to accurately calculate the resistance, the specific friction value needs to be obtained.

    According to Bi Duanguo's estimation of the first training, the wind speed of the general kitchen exhaust fume pipe is 10m s, and the specific friction resistance is 2 4Pa Specific friction resistance x length x additional coefficient) = 240Pa (external static pressure) The selected fan is full pressure External static pressure + fan resistance loss, so the full pressure of the fan is about 350Pa or so.

Related questions
2 answers2024-05-21

The grade, diameter and spacing of the reinforcement that need to be configured are determined by the calculation results of the design and in accordance with the specifications, and are not followed. >>>More

2 answers2024-05-21

The length of the meter needs to be 2100 300 = 7 blocks.

The width of the meter needs to be 1500 300 = 5 blocks. >>>More

6 answers2024-05-21

3 hp floor air conditioner is required.

According to the standards formulated by the national refrigeration department, 1 horse air conditioner is suitable for refrigeration area of 10 15 square meters, 10 19 square meters for horse, 16 26 square meters for horse, 15 30 square meters for horse, 2 horse for 20 37 square meters, 3 horsepower for 30 58 square meters, 5 horsepower for 50 65 square meters, and 6 horsepower for 60 70 square meters. >>>More

2 answers2024-05-21

The cost of decoration of a 40-square-meter house is mainly in the following aspects. >>>More

1 answers2024-05-21

It's a bit of a no-brainer. Visual inspection is generally only an approximation. The bed is not mentioned. >>>More